BS476-7 Fire retardant testing of building materials – Standard name:
BS476-7: Fire Tests on Building materials and structures – Method of test to determine the classification of the surface spread of flame of products
BS476-7: Flame retardant and fire protection test of building materials and building components – Determination of product flame surface burning level
BS476-7 Flame retardant and fire protection test of building materials - Scope of application of the standard:
surface of wall material
Exposed surface of insulation material
Exposed surface of ceiling material
According to the test results, the tested materials are divided into 4 levels according to the table. Class 4 materials have a high fire risk and are not allowed to be used as building materials.
level | Flame propagation degree during test 1.5 minutes | Degree of flame spread at the end of the test | ||
limit value mm | Allowable deviation value mm | limit value mm | Allowable deviation value of a test piece mm | |
1 | 165 | 25 | 165 | 25 |
2 | 215 | 25 | 455 | 45 |
3 | 265 | 25 | 710 | 75 |
4 | Values exceeding level 3 |
Relevant test standards
BS 476 : Fire testing of building materials and structures
BS 476-3 : Fire test of building materials and components - Fire test of exposed parts of roof
BS 476-4 : Fire testing of building materials and structures - Material non-flammability testing
BS 476-5 : Test method for flammability of building materials
BS 476-6 : Fire testing of building materials and components. Part 6: Test methods for fire spread of products
BS 476-7 : Fire testing of building materials and components. Part 7: Test methods for determining the surface spread classification of product flames
BS 476-11 : Fire test of building materials and components. Part 11: Determination method of thermal radiation of building materials
BS 476-12 : Fire test of building materials and components. Part 12: Test method for flammability of products in direct contact with flames
BS 476-13 : Fire test of building materials and components Part 13: Test method for flammability of products exposed to thermal radiation
BS 476-15 : Fire testing of building materials and structures - Test method for product heat release rate
BS 476-20 : Fire resistance testing of building materials and components. Part 20: Test methods for fire resistance of building components (general principles)
BS 476-21 : Fire resistance testing of building materials and components. Part 21: Test methods for fire resistance of load-bearing components
BS 476-22 : Fire test method for non-loaded building elements
BS 476-23 : Fire test of building materials and components. Part 23: Test method for the contribution of components to the fire resistance of components
BS 476-24 : Fire testing of building materials and components. Part 24: Test methods for fire resistance of ventilation ducts
BS 476-31.1 : Fire testing of building materials and components - Method of measurement of smoke penetration through door and window assemblies. Measurement method at room temperature
BS 476-33 : Fire testing of building materials and structures - Physical indoor testing of surface products