Emergency Lighting Test Equipment

Brief Introduction

ZONSKY Emergency Lighting Test Equipment is designed to assess the functionality, brightness, and reliability of emergency lighting and evacuation indicators under simulated fire conditions. This apparatus tests parameters such as luminance, battery backup duration, visibility in smoke-filled environments, and directional accuracy of exit signals. It is suitable for fire emergency lighting and evacuation indication systems installed in general industrial and civil buildings, as well as system lights with special performance installed in other environments.

 

Quick Quote

 

Apparatus Details

In compliance with:

  • ISO 30061:2007
  • EN 1838
  • IEC 60598-2-22
  • NFPA 101
  • AS 2293.1: Emergency escape lighting and exit signs for buildings – System design, installation and operation

 

Main Performance Parameters

Charge and Discharge Test

Parameter Specification
Battery charging test
Component surface temperature detection Uses wire diameter thermocouple to detect surface temperature of internal components
Battery charging current detection Detects overcharging current; maximum continuous current does not exceed 0.05Cₐ (0.05C₂₀A for lead-acid batteries)
Battery discharge detection
Termination voltage detection Adjustable with power supply voltage adjustment function; range is 50%–150% of rated voltage
Discharge current detection Detection range: 0.01mA–10mA; resolution: 0.01mA
Repeat conversion performance detection
Main power state time 0–99 minutes adjustable
Emergency state time 0–999 seconds adjustable
Repeat conversion times 0–999 times adjustable
State fluctuation performance test Uses power supply with voltage adjustment function; range: 50%–150% of rated voltage
Conversion accuracy Uses main power supply and voltage adjustment function; range: 50%–150% of rated voltage

 

Charge and Discharge Durability

Parameter Specification
Charge and discharge endurance times 0–999 times adjustable
Full charge time record 0–999 hours
Discharge time record 0–999 minutes

 

Insulation Resistance Test

Parameter Specification
Measurement range 1kΩ–10TΩ
Test voltage DC500V ± 50V
Voltage measurement accuracy ±(2% + 2 counts) for voltages ≥ 500V DC
Resistance measurement accuracy ±(5% + 2 counts) for voltages ≥ 500V DC
Timing 60s ± 5s

 

Withstand Voltage Performance Test

Parameter Specification
Test voltage AC 0–5kV
Leakage current AC 0–20mA
Test time 1–99 seconds
Transformer capacity 100VA
Measurement accuracy ±3% (±3 digits)

 

Grounding Resistance Test

Parameter Specification
Simultaneous display Displays test time, current, and resistance simultaneously
Constant current source Provides stable test current
Test voltage 10V
Test current 5–30A
Test resistance range 0–600mΩ
Accuracy ±5% (±3 characters)

 

Data Acquisition and Control

Parameter Specification
System Uses touch screen + PLC + modular acquisition and control