Applicable to sprinkler flow coefficient measurement.This equipment only provides sprinkler test device with nominal flow coefficient less than or equal to 115 as standard;
ZONSKY Sprinklers Flow Coefficient Measuring Apparatus is designed to determine the flow coefficient (K-factor) of sprinkler heads, a key parameter for sprinkler performance in fire suppression. This apparatus measures the flow rate through the sprinkler at various water pressures, calculating the K-factor, which reflects the sprinkler's discharge characteristics.
This equipment only provides sprinkler test device with nominal flow coefficient less than or equal to 115 as standard; sprinkler with nominal flow coefficient of 161 and 202 is optional test device, such sprinklers are used in special environments and are not commonly used.
Nominal flow coefficient range:
Nominal flow coefficient K | Flow Coefficient Range | Flow Coefficient Range for Dry Sprinklers |
57 | 54~60 | 52~62 |
80 | 76~84 | 74~86 |
115 | 109~121 | 106~124 |
ISO 6182-1:Fire protection - Automatic sprinkler systems - Part 1: Requirements and test methods for sprinklers.
EN 12259-1:Fixed firefighting systems - Components for sprinkler and water spray systems - Part 1: Sprinklers.
UL 199:Standard for Automatic Sprinklers for Fire-Protection Service.
NFPA 13:Standard for the Installation of Sprinkler Systems.
AS 2118.1:Automatic Fire Sprinkler Systems - Part 1: General Requirements.
1. Test medium: water
2. Test pressure: 0.1MPa-0.6Mpa;
3. Pressure measurement:
3.1 The pressure measurement is measured by hydraulic sensor;
3.2 Pressure measurement accuracy: greater than 0.4.
4. Flow measurement:
4.1 Use vortex flowmeter to measure;
4.2 Flow range: 0~500L/min;
4.3 Flow measurement accuracy: greater than 1.0;
5. Boosting method: booster cylinder;
6. Pressure regulation: the frequency converter is used, which is controlled and adjusted by the computer;
7. Medium temperature: room temperature;
8. Control mode: manual, computer control;
9. Program interface:
9.1 Flow coefficient: measure the flow rate of the sprinkler head every 0.10MPa, the pressure is from low to high, and then from high to low, thecomputer automatically calculates the flow coefficient K value and the average value of k for each pressure point;
9.2 Real-time pressure value display;
9.3 Real-time traffic display;
9.4 The above parameters are collected, recorded, saved and produced by computer and printed out;
10. Test sample: meet the test of 2 sprinklers at the same time.