HomeProducts Select by Industry Fire Equipment Testing Equipment Water Spray Impact Test Apparatus
Water Spray Impact Test Apparatus
  • Water Spray Impact Test Apparatus
  • Water Spray Impact Test Apparatus
Water Spray Impact Test Apparatus
Water Spray Impact Test Apparatus

Water Spray Impact Test Apparatus

When the building partition is subjected to the fire resistance test according to the fire resistance test method specified in ISO 834-1, the water spray impact test shall be additionally carried out as required.


Product Number:ZY6552
Share:
  • Product Description

 Water Spray Impact Test Apparatus

What is the Water Spray Impact Test Apparatus?


The Water Spray Impact Test Apparatus is designed to evaluate the water resistance and durability of materials and components when exposed to high-pressure water sprays. This apparatus subjects test specimens to controlled water impact forces, simulating conditions such as heavy rain or firefighting sprays. When the building partition is subjected to the fire resistance test according to the fire resistance test method specified in ISO 834-1, the water spray impact test shall be additionally carried out as required.


In the actual fire fighting and rescue, the building partition components may be impacted by the water spray of the fire hose, thus increasing the possibility of premature damage to the integrity of the building partition components. Therefore, we can consider its ability to resist the impact of water spray when designing building partition components. The types of building partition components include firewalls, fire partition walls, fire doors, fire shutters, fire windows, floor slabs, etc. When the above-mentioned components are subjected to the fire resistance test according to the fire resistance test method specified in ISO 834-1, a water spray impact test may be added as required.


Compliance:


ISO 5925-1:Fire tests - Smoke-control door and shutter assemblies - Part 1: Ambient and medium temperature leakage tests.


EN 1634-3:Fire resistance and smoke control tests for door and shutter assemblies, openable windows and elements of building hardware - Part 3: Smoke control doors and shutters.


NFPA 252:Standard Methods of Fire Tests of Door Assemblies


AS 1905.1:Components for the protection of openings in fire-resistant walls - Part 1: Fire-resistant door sets.


BS 476-31.1:Fire tests on building materials and structures - Methods for measuring smoke penetration through doorsets and shutter assemblies.



Main parameters:


1. Instrument composition: It is composed of pressure source, fire nozzle, fire hose, and fire connection short pipe;


2. Sources of pressure:


2.1 Water pressure: adjustable from 0.01Mpa to 0.35Mpa;


2.2 Flow rate: 8L/s;


2.3 Water storage tank: length 1.5m*width 1.5m*1m depth.


3. Fire-fighting water nozzle: a direct fire-fighting nozzle with a nominal interface diameter of Ф65mm and an equivalent nozzle diameter of 19mm; in line with Section 5.1.1.1 and Table 2 of GB8181-2005;


4. Fire hose: a lined fire hose with a specification of Ф65mm;


5. Fire-fighting connection short pipe: a stainless steel pipe with a diameter of Ф65mm and a length of 150mm.



Email to this supplier
  • To:
    ZONSKY INSTRUMENT CO., LTD
  • *E-mail:
  • *Message:

    Your message must be between 20-8000 characters

HomeProducts Select by Industry Fire Equipment Testing Equipment Water Spray Impact Test Apparatus

Home

Product

Phone

About Us

Inquiry