SHOP

Check Our Product

Bring to the table win-win survival strategies to ensure proactive domination. At the end of the day, going forward.

 

Description

Circuit Integrity Under Fire Conditions Apparatus

The Circuit Integrity Under Fire Conditions Apparatus is a specialized testing device designed to evaluate the operational resilience of electrical circuits exposed to fire. It subjects cables and wiring systems to high-temperature flame exposure while monitoring key parameters such as conductor continuity, insulation integrity, and circuit functionality throughout the test. This equipment provides essential data on the fire-resistance performance of electrical components.Talk To Our Team

Circuit Integrity Apparatus Compliance:

    • IEC 60331-11:1999 – Tests for electric cables under fire conditions – Circuit integrity – Part 11: Apparatus – Fire alone at a flame temperature of at least 750°C.
    • IEC 60331-12:2002 – Tests for electric cables under fire conditions – Circuit integrity – Part 12: Apparatus – Fire with shock at a temperature of at least 830°C.
    • IEC 60331-21:1999 – Tests for electric cables under fire conditions – Circuit integrity – Part 21: Procedures and requirements – Cables of rated voltages up to and including 0.61/1.0 kV.
    • IEC 60331-23:1999 – Tests for electric cables under fire conditions – Circuit integrity – Part 23: Procedures and requirements – Electric data cables.
    • IEC 60331-25:1999 – Tests for electric cables under fire conditions – Circuit integrity – Part 25: Procedures and requirements – Optical fiber cables.
    • IEC 60331-31:2002 – Tests for electric cables under fire conditions – Circuit integrity – Part 31: Procedures and requirements for fire with shock – Cables of rated voltages up to and including 0.61/1.0 kV.

Main Parameters

Parameter Specification
Supporting Gas Compressed air (air pressure >10MPa)
Flowmeter Two rotor flowmeters, adjustable air flow (0 to 200L/min) and gas flow (0 to 20L/min)
Thermocouple Installation Torch positioned 45mm (±x mm) horizontally and 70mm (±y mm) vertically from the thermocouple center
Verification Judgment Average thermocouple reading within (750±50)°C over 10 minutes, max difference ≤40°C
Ignition Device Chengming small flame ignition
Fire Time 0 to 99 minutes
Power Requirements AC380V (±10%) / 50Hz
Operating Power 1KW
Continuity Checking In compliance with GB/T 19216.21, GB/T 19216.23, and GB/T 19216.31
Heat Source Verification Uses K-type thermocouples (φ1.5mm mineral insulated stainless steel sheath)
Test Wall Non-combustible, non-metallic material (heat-resistant plate, 900mm height, 300mm width, 9mm thickness)
Torch Positioning Horizontal: 100mm to 120mm from thermocouple, Vertical: 40mm to 60mm downward
Circuit Integrity Apparatus tests the fire resistance of cables, Compliance:IEC 60331-11:1999/IEC 60331-12:2002/IEC 60331-21:1999/IEC 60331-23:1999

circuit integrity Apparatus

Let's Get In Touch

Please enable JavaScript in your browser to complete this form.

This website uses cookies to improve your experience. By using this website you agree to our Data Protection Policy.
Read more