Product Details
Emergency Lighting Test Equipment
Brief Introduction
ZONSKY Emergency Lighting Test Equipment is designed to assess the functionality, brightness, and reliability of emergency lighting and evacuation indicators under simulated fire conditions. This apparatus tests parameters such as luminance, battery backup duration, visibility in smoke-filled environments, and directional accuracy of exit signals. It is suitable for fire emergency lighting and evacuation indication systems installed in general industrial and civil buildings, as well as system lights with special performance installed in other environments.
Description
In compliance with:
- ISO 30061:2007
- EN 1838
- IEC 60598-2-22
- NFPA 101
- AS 2293.1: Emergency escape lighting and exit signs for buildings – System design, installation and operation
Main Performance Parameters
Charge and Discharge Test
| Parameter | Specification |
|---|---|
| Battery charging test | |
| Component surface temperature detection | Uses wire diameter thermocouple to detect surface temperature of internal components |
| Battery charging current detection | Detects overcharging current; maximum continuous current does not exceed 0.05Cₐ (0.05C₂₀A for lead-acid batteries) |
| Battery discharge detection | |
| Termination voltage detection | Adjustable with power supply voltage adjustment function; range is 50%–150% of rated voltage |
| Discharge current detection | Detection range: 0.01mA–10mA; resolution: 0.01mA |
| Repeat conversion performance detection | |
| Main power state time | 0–99 minutes adjustable |
| Emergency state time | 0–999 seconds adjustable |
| Repeat conversion times | 0–999 times adjustable |
| State fluctuation performance test | Uses power supply with voltage adjustment function; range: 50%–150% of rated voltage |
| Conversion accuracy | Uses main power supply and voltage adjustment function; range: 50%–150% of rated voltage |
Charge and Discharge Durability
| Parameter | Specification |
|---|---|
| Charge and discharge endurance times | 0–999 times adjustable |
| Full charge time record | 0–999 hours |
| Discharge time record | 0–999 minutes |
Insulation Resistance Test
| Parameter | Specification |
|---|---|
| Measurement range | 1kΩ–10TΩ |
| Test voltage | DC500V ± 50V |
| Voltage measurement accuracy | ±(2% + 2 counts) for voltages ≥ 500V DC |
| Resistance measurement accuracy | ±(5% + 2 counts) for voltages ≥ 500V DC |
| Timing | 60s ± 5s |
Withstand Voltage Performance Test
| Parameter | Specification |
|---|---|
| Test voltage | AC 0–5kV |
| Leakage current | AC 0–20mA |
| Test time | 1–99 seconds |
| Transformer capacity | 100VA |
| Measurement accuracy | ±3% (±3 digits) |
Grounding Resistance Test
| Parameter | Specification |
|---|---|
| Simultaneous display | Displays test time, current, and resistance simultaneously |
| Constant current source | Provides stable test current |
| Test voltage | 10V |
| Test current | 5–30A |
| Test resistance range | 0–600mΩ |
| Accuracy | ±5% (±3 characters) |
Data Acquisition and Control
| Parameter | Specification |
|---|---|
| System | Uses touch screen + PLC + modular acquisition and control |